A is two coils of wire on a soft-iron core. It changes the size of an alternating voltage: more turns on the output coil than on the input coil give a bigger voltage, fewer turns a smaller one. The grid uses transformers to send electricity along cables at a very high voltage, so the current is small and less energy is wasted heating the cables.
You'll be able to
Describe how a transformer is built, and use the words primary, secondary, step-up and step-down.
Use VsVp=NsNp to find a voltage or a number of turns.
Describe how transformers are used to send electricity at high voltage, and state the advantages.
Explain how a transformer works, using .
Use IpVp=IsVs for a 100% efficient transformer.
Use P=I2R to explain why cables waste less when the voltage is higher.
Before you start3 quick questions on what this builds on
Check yourself
A coil of wire is connected to a sensitive meter. Which of these induces an e.m.f. in the coil?
Check yourself
What is an (a.c.)?
Check yourself
An appliance has a power of 1150W on a 230V supply. What is the current in it, in A?
A changes an alternating voltage into a bigger or a smaller one. Mains electricity is about 230V in many countries, for example, but a doorbell might need only 8V.
It has two coils of insulated copper wire wound on a closed loop of soft iron, the core. The two coils are not joined to each other by any wire.
The secondary has more turns than the primary, so this transformer steps the voltage up.
The is connected to the a.c. supply: it is the input. The gives the output, to a lamp or any other device.
Each material has a job. Copper is a good conductor, so the coils waste little energy. The insulation stops the current jumping between turns. Soft iron is easily magnetised and demagnetised (a ), so it carries the magnetic field from one coil to the other.
A has more turns on the secondary coil than on the primary, so the output voltage is bigger than the input. A has fewer turns on the secondary, so the output voltage is smaller.
A transformer works only with . The changing current in the primary makes a changing , and only a changing field induces a voltage in the secondary (4.5.1). A steady d.c. makes a steady field, so there is no output, apart from a brief flick at the moment the d.c. is switched on or off.
Transformers have a high , but they still warm up: the current heats the coils and the changing field heats the core. This wasted energy goes to the thermal store of the surroundings.
Worked exampleDescribe the construction of a simple step-down transformer.
Try it first, then reveal one step at a time.
Name the parts: two coils and a core.
Say what each is made of.
Say which coil is the input and which is the output.
Finish with the turns: in a step-down transformer the output coil has fewer.
It has two coils of insulated copper wire. The coils are wound on a soft-iron core, which links them. The primary coil is connected to the a.c. input and the secondary coil gives the output. There are fewer turns on the secondary coil than on the primary.
Check yourself
The primary coil of a transformer has 2000 turns and the secondary has 150 turns. What type of transformer is it?
Check yourself
The primary coil of a transformer is connected to a battery, so a steady current flows in it. What does a voltmeter across the secondary coil read while the current stays steady?
How a transformer works Extended only
A transformer uses , step by step:
1. The alternating current in the primary coil makes a magnetic field, as in an . The current keeps changing size and direction, so the field does too.
2. The soft-iron core is magnetised by this field (). It links the field to the secondary coil, so the changing field passes through the secondary too.
3. A changing magnetic field through a coil induces an e.m.f. in it. The field keeps reversing, so the induced e.m.f. across the secondary is alternating.
4. If the secondary is part of a complete circuit, this e.m.f. drives an alternating current round it. An e.m.f. is induced in every turn and the turns add up, so more turns give a bigger output.
Worked exampleExplain how an alternating current in the primary coil of a transformer produces an alternating e.m.f. across the secondary coil.
Try it first, then reveal one step at a time.
Start with the primary coil and the field it makes.
Say what the core does.
Use induction to link the field to the secondary.
Explain why the output alternates.
The a.c. in the primary coil sets up a magnetic field that keeps changing. The soft-iron core links this field to the secondary coil. The changing field through the secondary induces an e.m.f. across it. The field reverses each time the primary current reverses, so the induced e.m.f. alternates too.
Check yourself
In a transformer, what links the primary coil to the secondary coil?
Voltages and turns
The voltages across the two coils are in the same ratio as their numbers of turns. Here Vp and Vs are the across the primary and secondary coils, and Np and Ns are their numbers of turns.
Learn this
VsVp=NsNp
To find the output voltage, rearrange to Vs=Vp×NpNs. Then check the answer makes sense: a step-down transformer must give a smaller voltage.
Worked exampleIn a battery charger, the transformer's primary coil of 4600 turns is connected to the 230V mains. Its secondary coil has 100 turns. Calculate the output voltage.
Try it first, then reveal one step at a time.
Write the equation: VsVp=NsNp.
Rearrange: Vs=Vp×NpNs.
Substitute: Vs=230×4600100=5.0V.
Check: the secondary has fewer turns, so the voltage should go down. It does.
Vs=5.0V
Worked exampleA transformer must change a 12V a.c. supply into 330V. Its primary coil has 160 turns. Calculate the number of turns needed on the secondary coil, and state the type of transformer.
Try it first, then reveal one step at a time.
Rearrange the equation for Ns: Ns=Np×VpVs.
Substitute: Ns=160×12330=4400.
State the type: the voltage goes up, so it is a step-up transformer. The secondary has more turns, as it should.
Ns=4400
Check yourself
The input voltage to a transformer is 120V. Its primary has 1500 turns and its secondary 375 turns. What is the output voltage, in V?
Check yourself
A transformer changes 230V to 46V. Its secondary coil has 90 turns. How many turns are on its primary coil?
Extended only
If a transformer is 100% efficient, no energy is wasted, so the into the primary equals the power out of the secondary. Electrical power is current × p.d., P=IV.
Extended only
Learn this
IpVp=IsVs
Extended only
So when a 100% efficient transformer steps the voltage up, it steps the current down by the same factor.
Extended only
Worked exampleA 100% efficient transformer steps 230V mains down to 11.5V for a set of garden lights. The current in the secondary coil is 4.0A. Calculate the current in the primary coil.
Try it first, then reveal one step at a time.
Write the equation: IpVp=IsVs.
Rearrange: Ip=VpIsVs.
Substitute: Ip=2304.0×11.5=0.20A.
Check: the voltage is stepped down, so the primary current should be smaller than the secondary current. It is.
Ip=0.20A
Extended only
Check yourself
A 100% efficient transformer has 8 times as many turns on its secondary coil as on its primary coil. How does the secondary current compare with the primary current?
Sending electricity at high voltage
Power stations are often far from the towns they supply. The long cables have , so the current heats them and wastes energy.
Step up at the power station, step down near the users.
1. At the power station, a step-up transformer raises the voltage to a very high value, often hundreds of thousands of volts.
2. Cables on pylons, or under the ground, carry the electricity across the country.
3. Near towns, step-down transformers lower the voltage in stages, down to the mains voltage used in homes.
A smaller current heats the cables less. This gives the advantages of high-voltage transmission: less energy is wasted as heat in the cables, so more of it reaches the users. Thinner, lighter and cheaper cables can also carry the smaller current.
Worked exampleA power station sends 60MW of electrical power along its cables at 400kV. Calculate the current in the cables.
Try it first, then reveal one step at a time.
Convert to watts and volts: 60MW=60×106W and 400kV=400×103V.
Rearrange P=IV: I=VP.
Substitute: I=400×10360×106=150A.
Compare: sending the same power at 25kV would need I=25×10360×106=2400A, 16 times as much.
I=150A
Worked exampleState two advantages of transmitting electricity at a high voltage.
Try it first, then reveal one step at a time.
"State" needs short answers, no long explanation.
Give two separate points, each linked to the smaller current.
Less energy is wasted as heat in the cables, because the current in them is smaller. Thinner, cheaper cables can be used to carry the smaller current.
Check yourself
Why is electricity sent across the country at a very high voltage?
Check yourself
A power line carries 18MW at 275kV. What is the current in the line, in A? Give your answer to 2 significant figures.
Extended only
The power wasted as heat in a cable depends on the current in it and its resistance R:
Extended only
Learn this
P=I2R
Extended only
The current is squared. In the same cable, halve the current and the power wasted falls to a quarter. So stepping up the voltage, which cuts the current, makes a big difference.
Extended only
Worked exampleThe cables in the example above have a total resistance of 2.5Ω. The station sends 60MW at 400kV, so the current is 150A. Calculate the power wasted in the cables.
Try it first, then reveal one step at a time.
Write the equation: P=I2R.
Substitute: P=1502×2.5=56250W.
Round to 2 significant figures: about 56kW, less than 0.1% of the power sent.
P≈56kW
Extended only
Worked exampleUse P=I2R to explain why less power is wasted in transmission cables when the voltage is higher.
Try it first, then reveal one step at a time.
Link voltage to current first, for the same power.
Then use P=I2R with the cables' resistance fixed.
For the same power, P=IV, so a higher voltage means a smaller current in the cables. The power wasted heating the cables is P=I2R. The resistance of the cables is the same, so a smaller current means less power is wasted. Because the current is squared, halving the current cuts the wasted power to a quarter.
Extended only
Check yourself
A fixed power is sent along a cable. The voltage is doubled. What happens to the power wasted in the cable?
Common mistakes
Turning the turns ratio upside down. In a step-down transformer the primary has more turns than the secondary; check your answer against this.
Extended: thinking a step-up transformer increases the current as well as the voltage. Energy is not created, so when the voltage goes up the current goes down.
Saying high-voltage transmission is "faster" or "safer". The advantage is a smaller current, so less energy is wasted heating the cables.
Forgetting to convert MW to W or kV to V before using P=IV. The current comes out a thousand or a million times wrong.
Extended: forgetting to square the current in P=I2R. In the same cable, halving the current cuts the wasted power to a quarter, not a half.
Exam tips
"Describe the construction": name two coils of insulated copper wire, a soft-iron core, and which coil has more turns. Each point can earn a mark.
"Calculate" with the turns equation: write it, substitute, then give the answer with its unit. Check that step-down gives a smaller voltage.
"State" the advantages of sending electricity at high voltage as two separate points, such as less energy wasted heating the cables and thinner, cheaper cables.
"Explain" how a transformer works (Extended): link every step: a.c. in the primary, changing magnetic field, core links it to the secondary, e.m.f. induced in the secondary.
Key takeaways
Learn thisA transformer is two coils of insulated copper wire on a soft-iron core. It works only with a.c., because only a changing magnetic field induces a voltage in the secondary.
Learn thisStep-up: more turns on the secondary than the primary, so the output voltage is bigger. Step-down: fewer turns on the secondary, so the output voltage is smaller.
Learn thisVsVp=NsNp
Learn thisTransmission: a step-up transformer at the power station, step-down transformers near the users. For the same power, raising the voltage lowers the current, so less energy is wasted heating the cables and thinner, cheaper cables can be used.
Learn thisHow it works: a.c. in the primary makes a changing magnetic field; the soft-iron core links it to the secondary; the changing field induces an alternating e.m.f. across the secondary.